Products - Initiating Devices
PHOTOELECTRIC
Photoelectric type smoke detector head, low profile, plugs into a mounting base, 3 year warranty, operating temperature range from -20° F to + 150° F
Conventional Ionization
Ionization type smoke detector head, low profile, plugs into a mounting base, 3 year warranty, operating temperature range from -20° F to + 150° F
Resettable heat detector
Plug-in type heat detectors, Rate-of-Rise & Fixed or Fixed temperature only. Alarm point ranges from 135° F to 200° F. Needs a mounting base to plug into. Resettable unit.
NON-RESETTABLE
Pancake heat detector, non-resettable. Rate-of-Rise & Fixed or Fixed temperature only. Alarm point ranges from 135° F to 200° F.
REFLECTIVE SELF-ADJUSTING
The most advanced reflective beam smoke detector in the world. Coverage ranges from 15 ft. to 300 ft. When the building settles over time, the beam detector automatically realigns its beam sensor to the sweet spot (alignment), which ensures maximum performance without nuisance service calls, 4-wire 24VDC operating voltage.
END-TO-END
End-to-end beam smoke detection that comes with a transmitter and receiver. 4 wire 24VDC operating voltage.
PCVS
Control Valve Supervisory Switch, single or double contacts.
IONIZATION
XP-95 Series ionization smoke detector head. Unique addressing in the base so detectors can be replaced with any programming. Requires a mounting base.
MULTI-CRITERIA
XP-95 Series photoelectric smoke detector & heat sensor combination unit/head. Unique addressing in the base so detectors can be replaced with any programming. Requires a mounting base.
STANDARD 6"
Mounting base for XP-95 and Discovery series intelligent detectors, universal mounting, 6 inch diameter.
RELAY
Mounting base for XP-95 and Discovery series intelligent detectors, universal mounting, 4 inch in diameter.
100M
2-wire intelligent reflective beam detector, high quality and easy to install. Coverage ranges from 150 ft. to 300 ft. in length and 30ft. wide. Alignment LEDs guide the installer for quick and easy installation, 24VDC operating voltage.
Conventional Manual Pull Station
Durable manual pull stations made of metal with a mini-addressable module. Options range from single action; double action; key lock/reset; phone jack; gold contacts; institutional (no pull lever, key activation); special colors; ect.
DUAL MONITOR MODULE
Addressable monitor module, XP95 series, mounts on a standard 4 x 4 electrical box (1900 box). Two (2) addresses in one module. Typically used for monitoring 2 devices in a close proximity ie. sprinkler waterflow and a tamper device.
RELAY MODULE
Addressable relay module (dry contact), XP95 series, mounts on a standard 4 x 4 electrical box (1900 box). This unit also comes with a built-in monitor module.
SOUNDER MODULE
Addressable sounder control module, XP95 series, mounts on a standard 4 x 4 electrical box (1900 box). This unit is used to extend a notification circuit out in the field. The output is supervised with a resistor.
ADDRESSABLE ISOLATION MODULE
SLC loop isolation module, used to protect a circuit against a short. When a short is placed on the SLC, the isolation module before and after the short opens that section of the SLC. This allows the rest of the SLC to operate and continue protection/detection until the short is fixed.
DOOR HOLDERS
The DH series fire door holders are constructed of the finest materials and workmanship available. The door holder is made of durable die-cast metal finished in high luster double chrome or brass plating. Other features include standard dual voltage dc or ac inputs of 12 & 24V, 24 & 120V and 24 & 220V models. While reducing stocking requirements, the DH-24120 draws a mere .020 mA @ 24VDC lowering overall job costs (in large installations the cost savings can be substantial).
PULL STATION COVER WITH HORN OPTION
Global Fire Control's manual pull station cover is a rugged poly-carbonate cover used to help protect manual pull stations and other devices from false alarms, vandalism, dust and weather. It comes in a variety of figurations to satisfy most applications. It meets the requirements of the Americans with Disabilities Act (ADA). Specifically, it has been tested by Underwriter's Laboratories, for compliance with the 5lb. pull force requirement. In addition, the total depth of the unit when mounted is less than the required 4 inches.
AUXILIARY RELAYS
The MR Series Multi-voltage Control Relays offer SPDT or DPDT 10 Amp resistive contacts which may be operated by one of four input control voltages. A single relay may be energized from a voltage source of 24VDC, 24VAC, 120VAC or 230VAC by wiring to appropriate input terminals. Each relay position contains a red LED, which indicates the relay coil is energized. Relays may be "snapped apart" from a standard 4 module assembly and used independently. These Devices are Ideal for applications where local contacts are required for system status, remote contacts for control of electrical loads and general purpose switching.
Addressable Air Duct Smoke Detector
2-WIRE
Intelligent/Addressable air duct smoke detector, photoelectric type, 2-wire without built-in relay. It needs a sampling tube and has remote LED options.
4-WIRE
Intelligent/Addressable air duct smoke detector, photoelectric type, 4-wire with built-in relay that follows the detector alarm relay. It needs a sampling tube and has remote LED options. 24VDC operating voltage
Addressable Flame detector
ADDRESSABLE FLAME DETECTOR
The 2-wire intelligent Dual IR Flame Detectors are designed to detect either the ultraviolet (UV) or the infra-red (IR) radiation emitted by a fire. The Apollo XP95 Dual Infra-red (IR) Flame Detector detects infra-red radiation by using 2 different IR radiation sensors which respond to different infra-red wavelengths at the upper end of the spectrum. This allows the XP95 Flame Detector to distinguish between flames and spurious sources of radiation, for example sunlight.
addressable heat detector
ADDRESSABLE HEAT DETECTOR
XP-95 Series heat sensor/detector head. Unique addressing in the base so detectors can be replaced with any programming. Requires a mounting base.
Addressable Monitor Modules (Input)
MINI-MONITOR
Mini-addressable monitor module, XP95 series, comes with flying leads for connection to manual pull stations or other N.O. contacts. Fits into a single gang box.
MONITOR MODULE
Addressable monitor module, XP95 series, mounts on a standard 4 x 4 electrical box (1900 box). Typically used for monitoring sprinkler waterflow and tamper devices or 4-wire detectors.
Addressable Mounting Bases
Addressable Reflective Beam Detector
Addressable Smoke Detectors
Addressable Photoelectric
XP-95 Series photoelectric smoke detector head. Unique addressing in the base so detectors can be replaced with any programming. Requires a mounting base.
Conventional Heat Detectors
Conventional Beam Type Smoke Detector
50M